L1Calo rack layout in USA15


Rationale

The layout of the racks for the L1Calo trigger on niveau 2 of USA15 is shown in this diagram. There is another diagram. showing the layout of the racks for the Muon trigger on niveau 1.

The main considerations for the calorimeter trigger are:

Other comments:

Estimate of cable lengths

A rough calculation of cable lengths in this layout is given below. Dont take the decimal points seriously.

The basic assumptions are:

The lengths of the long signal cables from the detectors will be
determined by Technical Coordination. For the purposes of looking
at various rack layouts, it is useful to estimate the length from
the holes to the outermost racks in a particular layout.

Signal cables from holes to outermost receivers:
(A side) horiz:   5.5*0.6 = 3.3m    (C side) horiz:   4.5*0.6 = 2.7m
         forward:           1.5m             forward:           1.5m
         upwards:           2.5m             upwards:           2.5m
                            ----                                ----
                            7.3m                                6.7m

Signal cables from holes to TileCal patch panels (1 rack further):
(A side) horiz:   6.5*0.6 = 3.9m    (C side) horiz:   5.5*0.6 = 3.3m
         forward:           1.5m             forward:           1.5m
         upwards:           2.5m             upwards:           2.5m
                            ----                                ----
                            7.9m                                7.3m

TileCal patch panels to receivers (depends on receiver layout):
(both sides) horiz: 3.0*0.6 = 1.8m
  fwd/back/up/down:          ~4.2m
                              ----
                              6.0m 

Receivers to PPMs:
(both sides) horiz: 4.0*0.6 = 2.4m
  fwd/back/up/down:          ~3.6m
                              ----
                              6.0m 

PPMs to CPMs (LVDS cables):
(A side) horiz:     9*0.6 = 5.4m    (C side) horiz:     6*0.6 = 3.6m
         fwd/back:          1.0m             fwd/back:          1.0m
         up/down:   2*2.5 = 5.0m             up/down:   2*2.5 = 5.0m
                            ----                                ----
                           11.4m                                9.6m

PPMs to JEMs (LVDS cables):
(A side) horiz:     7*0.6 = 4.2m    (C side) horiz:     7*0.6 = 4.2m
         fwd/back:          1.0m             fwd/back:          1.0m
         up/down:   2*2.5 = 5.0m             up/down:   2*2.5 = 5.0m
                            ----                                ----
                           10.2m                               10.2m

Between CMMs:
(a) via hole between racks:    CP: 1.5m,  JEP: 1.0m
(b) via underfloor cable tray: CP: 4.0m,  JEP: n/a

NB option (a) was mentioned to Mark Hatch a long time ago without
raising strong objections, so the shorter path is assumed below.

CMM to CTP (with present CTP position on niveau 1):
CP system:  horiz:  3*0.6 = 1.8m    JEP system: horiz:  2*0.6 = 1.2m
            fwd/back:       1.0m                fwd/back:       1.0m
            downwards:     ~4.0m                downwards:     ~4.0m
                            ----                                ----
                            6.8m                                6.2m


Longest cable lengths from the Receivers to the CTP:
CP system:   6.0 + 11.4 + 1.5 + 6.8 = 25.7m (ie about 5.1 BCs)
JEP system:  6.0 + 10.2 + 1.0 + 6.2 = 23.4m (ie about 4.7 BCs)

Including the TileCal patch cables:
CP system:   6.0 + 6.0 + 11.4 + 1.5 + 6.8 = 31.7m (ie about 6.3 BCs)
JEP system:  6.0 + 6.0 + 10.2 + 1.0 + 6.2 = 29.4m (ie about 5.9 BCs)

The present layout is optimised to reduce the total cable length for
the JEP system. If the CP system has the worst latency, the positions
of the JEP and CP racks could be swapped. This would reduce the total
CP cable from ~26m to ~25m and increase the JEP from ~23m to ~25m
(plus TileCal patch cables).


The Glink cables dont affect the latency, but estimates of the lengths
we expect are required for bit error rate testing of these lengths.
The cablse from the PPMs come from the back of each module, so may
have to go down under the floor at some point (certainly from the A
side) whereas those output from the front of the CPMs/JEMs can go
directly across the front of the racks to the ROD front panels.

Glink cables to RODs:
PP (A side):    10*0.6 + 1.0 + 5.0 = 12.0m  (under floor)
PP (C side):     4*0.6 + 1.0 + 5.0 =  8.4m  (under floor)
CP/JEP (max):    4*0.6 + 0.5 + 2.0 =  4.9m  (across front)


Last updated on 27-May-2003. Send comments on this page to Murrough Landon